Achieved the highest level of temperature control ±0.1°C and humidity control ±1°C in the small size class.
| Process air volume | 0.3~4.0m3 |
| Temperature control accuracy | ±0.1℃ |
| Temperature setting range | 18~30℃ |
| Humidity control range | ±1% |
| Set humidity range | 45~75% |
| Efficiency | Settable temperature and humidity range ※1 | ℃,% | 18~30,45~75 |
| Temperature and humidity control accuracy ※2 | ℃,% | ±0.1,±0.1 | |
| Cooling + heating capacity(50/60Hz) | kW | 1.3 / 1.4 | |
| (Maximum cooling capacity) | (kW) | (0.9) / (1.0) | |
| Rated treatment airflow | m3/min | 0.7~1.0 | |
| Maximum external static pressure ※3 | Pa | 120 / 160 | |
| Ambient temperature/humidity range(supply air) ※1 | ℃,% | 15~35,30~70 | |
| Environmental conditions | Suction temperature change gradient | ℃/h | Within ±1 |
| Intake humidity change gradient | %/h | Within ±5 | |
| External Dimensions of Main body ※4 | mm | W350 × D600 × H750 | |
| Product weight | kg | 70 | |
| Control air outlet | mm | φ | |
| Humidifying water | quality of water | Pure water (Conductivity1~10μS/cm) |
|
| Maximum humidifying capacity ※5 | kg/h | 0.8 | |
| Supply temperature range | ℃ | 10~40 | |
| Connection Bore | Rc1/4 | ||
| Electrical Properties |
Power Supply ※6 | V(Hz) | 1φ100V±10%(50/60) |
| Amount of electricity consumed | kW | 1.2/1.2 | |
| Operation control method | Heat pump balance control | ||
- It does not represent a controllable temperature/humidity range. The controllable temperature/humidity range depends on the inlet air temperature and humidity.
- When suction air temperature and humidity are stable. Accuracy of controller display value at one discharge point. At rated maximum airflow.
- External static pressure when operating at maximum rated treatment airflow with throttling at the control air discharge side.
- Height includes the discharge port.
- At maximum humidification operation within the specification range.
- Power supply voltage unbalance should be within ±3%.